Education

Lunch and Learn:Engineered Equipment Inc. strives to be the leading provider of training and educational opportunities in the Oklahoma HVAC market. We host many Lunch and Learn presentations at our offices, and also take specific topics to individual customers upon request. The majority of our Lunch and Learn presentations qualify for PDH(s) (Professional Development Hour(s)). Don’t hesitate to contact us if you have a training or educational need!
Look for more information via our website and email on upcoming Lunch and Learn topics.
Videos
Basics of HVAC
Please visit this link for a training video on HVAC systems. This video covers the basic terminology all the way up to selection of equipment.
Chilled Beam Overview
Please visit this link for info on all Price Chilled Beams
Smoke Test Videos
Please visit this link for video demonstrations of different diffusers types and applications.
HVAC Training Classes
Please visit this link for various HVAC training classes.
Software
AAON
Greenheck
Price
Temtrol
Apps
Greenheck
Munters
Useful Formulas
– Air Changes Per Hour(ACH) = (CFM x 60) / Room Volume ft3
– CFM = Room Volume ft3 x (Air Changes Per Hour / 60)
– %OA = (RAT – MAT) / (RAT – OAT) x 100
– OAT = (MAT x 100) – (%RA x RAT) / %OA
– MAT = (%OA x OAT) + (%RA x RAT) / 100
– RAT = (MAT x 100) – (%OA x OAT) / %RA
– QTOTAL(Btu/Hr) = 4.5 x cfm x Δh(Btu/lb)
– Cooling Load(tons) = 4.5 x cfm x Δh(Btu/lb) / 12,000
– QLATENT(Btu/Hr) = .68 x cfm x ΔW(grains/lb)
– Humidification Load(lb/Hr) = 4.5 x cfm x ΔW(grains/lb) / 7,000
– QSENSIBLE(Btu/Hr) = 1.08 x cfm x ΔT(oF)
– Electric Heat Capacity(KW) = 1.08 x cfm x ΔT(oF) / 3,414
– Gas Heating(MBH) = 1.08 x cfm x ΔT(oF) / 1,000
– CFM = Room Volume ft3 x (Air Changes Per Hour / 60)
– %OA = (RAT – MAT) / (RAT – OAT) x 100
– OAT = (MAT x 100) – (%RA x RAT) / %OA
– MAT = (%OA x OAT) + (%RA x RAT) / 100
– RAT = (MAT x 100) – (%OA x OAT) / %RA
– QTOTAL(Btu/Hr) = 4.5 x cfm x Δh(Btu/lb)
– Cooling Load(tons) = 4.5 x cfm x Δh(Btu/lb) / 12,000
– QLATENT(Btu/Hr) = .68 x cfm x ΔW(grains/lb)
– Humidification Load(lb/Hr) = 4.5 x cfm x ΔW(grains/lb) / 7,000
– QSENSIBLE(Btu/Hr) = 1.08 x cfm x ΔT(oF)
– Electric Heat Capacity(KW) = 1.08 x cfm x ΔT(oF) / 3,414
– Gas Heating(MBH) = 1.08 x cfm x ΔT(oF) / 1,000